Standard function blocks
250
02/16 MN05013001Z EN
Contact
The contact of the function block is evaluated in the standard
circuit diagram. It closes for the on time and opens for the
off time on the defined days.
Memory requirement
The 7-day time switch function block requires 68 bytes of
memory plus 4 bytes per channel used.
Operation of the function block
The switching points are defined according to the
parameters entered.
MO to FR: on weekdays Mo, Tu, We, Th, Fr
ON 10:00, OFF 18:00: On and off time on each weekday.
MO: Every Monday
ON 10:00: On time
SA: Every Saturday
OFF 18:00: Off time
Switching on working days
Time switch HW01 switches on from Mondays to Fridays
with channel:
• A between 6:30 and 9:30.
• B between 17:00 and 22:30.
Parameters
Function
HW..Q1
Switch contact
HW01 B +
>DY1 MO
>DY2 FR
>ON 17:00
>OFF 22:30
HW01 A +
>DY1 MO
>DY2 FR
>ON 06:30
>OFF 09:30