Safety function blocks
414
02/16 MN05013001Z EN
Muting sensors
The setting of this parameter depends on the arrangement
of muting sensors and the muting procedure selected.
Discrepancy time
The discrepancy time LM..DT can be set when activated for
2-channel light curtain monitoring.
easySafety is factory set with a discrepancy time of 3.0 s.
Parameters
Function, parameterisation in the func-
tion block
2P
Use of 2 sensors A1 and A2 for parallel muting,
crossed arrangement (default settings)
2S
Use of 2 sensors A1 and A2 for serial muting,
adjacent arrangement
4P
Use of 4 sensors A1, A2 and B1, B2 for parallel
muting, opposing arrangement
4S
Use of 4 sensors A1, A2 and B1, B2 for sequen-
tial muting, adjacent arrangement
Parameters
Function, parameterisation in the func-
tion block
>DT
OFF; 0.5 - 3.0 s; adjustable in increments of
g?
?
5 s