Standard function blocks
252
02/16 MN05013001Z EN
Time overlaps
The time settings of a time switch overlap. The clock
switches on at 16:00 on Monday, whereas on Tuesday and
Wednesday it switches on at 10:00. On Monday to
Wednesday the switching-off time is 22:00.
Figure 108: Signal diagram of overlaps
HW04 A +
>DY1 MO
>DY2 WE
>ON 16:00
>OFF 22:00
HW04 B +
>DY1 TU
>DY2 WE
>ON 10:00
>OFF 00:00
h
On and off times of output Q1 always follow the channel
which switches first. In other words, the first On time at
one of the four channels switches the state at output Q1
to 1.
The first Off time of a channel switches the state at output
Q1 to 0.
If the On and Off times occur at the same time, output Q1
is switched off.