HY, year time switch
263
02/16 MN05013001Z EN
Configuring the parameters for continuous periods of
time
The following examples show how to configure the parame-
ters for continuous periods of time in which the time switch
remains continuously switched on. The parameter definition
is carried out in pairs on two adjacent channels..
Example 6: Time range for each year (2-channel)
The year time switch HY01 is required to switch on at 00:00
on day 02.05 of each year and stay on continuously until
00:00 on 1.11 of each year. “Open air season”.
Figure 116:
Select time range for each year
Parameter settings of the year time switch HY01:
ON/OFF
: First/last
switch-on years are not
restricted in this case.
ON/OFF
: First/last
switch-off years are not
restricted in this case.
31/10
... 2010
2011
31/10
31/10
31/10
2/5
2/5
2/5
2012 ...
HY01
A
+
>ON 02.05.--
>OFF --.--.--
HY01 B
+
>ON --.--.--
>OFF 31.10.--