Changing function block parameters
A easySafety device allows you to change the parameters of
standard function blocks, such as the setpoints of timing or
counter relays without calling up the circuit diagram. To
change these parameters, the easySafety device must be in
RUN mode.
With safety function blocks, parameters can only be changed
via the safety circuit diagram and only then if the easySafety
device is in STOP mode. The procedures for changing
parameters of a safety or standard function block are
different:
Changing safety function block parameters
Requirement: The easySafety device must be in STOP mode!
Proceed as follows to call the parameter dialog again for
changes:
X
Select the safety function block in the safety circuit
diagram.
X
Press OK to enter Entry mode.
X
Move to the function block number and press OK.
The parameter dialog opens.
X
Press OK or cursor button
í
to move to the parameter to
be changed.
X
Change the parameters required, e.g. the time range M:S
(Minute:Second) to S (Second) and exit the parameter
dialog with ESC.
The easySafety device returns to the safety circuit diagram.