Safety function blocks
496
02/16 MN05013001Z EN
Parameters
When using the function block in the circuit diagram for the
first time, press OK to enter the general display of the func-
tion block parameters automatically, as shown in the figure
on the left for an on-delayed timing relay. Enter the function
block settings here. The display contains the following
elements:
Zeitwert
The parameters consist of the following:
Operating mode
The Operating mode parameter defines the switch function
of the timing relay.
TS01 S
X
*
*** ***
>T1
000
>T2
000
TS01
Function block: Safety timing relay No. 01
X
Operating mode: On-delayed
S
Time range: Seconds
>T1
Time value T1: 000s.000ms
>T2
Time value T2: 000s.000ms
Parameters
Switch function
X
On-delayed switching (one time value required)
â
Off-delayed switching (one time value required)
X
â
On and off-delayed (two time values required)
#
Off delayed switching, setpoint retriggerable
(one time value required)
ü
Single pulse switching (one time value
required)
Ü
Flash switching (two time values required)