LC, light curtain
397
02/16 MN05013001Z EN
Startup test
The protected area must be explicitly interrupted for the
startup test and the Reset command initiated.
The startup test is carried out
• Every STOP-RUN change of the easySafety device.
• Every time the function block is deactivated and then acti-
vated with the EN enable coil.
The startup test is further described in section “Parameter
SUT (Startup test)” on page 347.
Discrepancy time
The discrepancy time LC..DT can be set when activated for 2-
channel light curtain monitoring.
easySafety is factory set with a discrepancy time of 3.0 s.
Parameters
Function, parameterisation in the func-
tion block
OFF
No startup test required (default setting)
SUT
The startup test must be carried out
Parameters
Function, parameterisation in the func-
tion block
>DT
OFF; 0.5 - 3.0 s; adjustable in increments of
g
0.5 s