Diagnostics
621
02/16 MN05013001Z EN
F008
61448
Error: Frequency measuring range exceeded
(>1250 Hz).
F009
61449
Error: Different input frequencies.
F00A
61450
Error: No pulses on one channel.
F00B
61451
Error: Reset and inputs operated on function block
startup.
F00C
61452
Error: Reset and OC operated on function block
startup.
F00E
61454
Error: Only one channel was opened and closed.
F00F
61455
Error: Undefined switch position.
F010
61456
Error: Position 2 not permissible after panic posi-
tion.
F011
61457
Error: Feedback circuit not opened after time.
F012
61458
Error: Feedback circuit not closed after time.
F013
61459
Error: Reset operated on function block startup.
F014
61460
Error: More than one operating mode selected at
the same time.
F015
61461
Error: No operating mode selected.
F016
61462
Error: Short circuit in input channel after 24 V.
F017
61463
Error: Short circuit in input channel after 24 V.
F018
61464
Error: At least one input operated on function block
startup.
F019
61465
Error: Implausible processing sequence.
F01A
61466
Error: Muting sequence completed, light curtain
not free.
F01B
61467
Error: Clearing completed; light curtain or sensors
not free.
Status number
Plain text
Hexadecimal (0–F)
decimal (0-9)