Example 3
: Copying of marker blocks, definition of a range
in a different format
Marker range MD60 to MD62 is to be copied to MW40 to
MW45.
• Parameters of function block BT01:
– Source range:
>I1 MD60
– Destination range: >I2 MW40
– Number of bytes:
>NO 12
After a rising edge from 0 to 1 at coil BT01T_ the values are
copied to the appropriate range.
h
The transfer is in byte format. 12 bytes are to be copied.
The range MD60 to MD62 is 12 bytes. This is copied to the
range MW40 to MW45.
Comparison
range 1
Value of marker range 1
(decimal/binary)
Comparison
range 2
Value of marker range 2
(decimal/binary)
MD60
866143319/
0011001110100000
0100110001010111
MW40 (LSW)
19543/0011001110100000
0100110001010111
MD60
866143319/
0011001110100000
0100110001010111
MW41 (MSW)
13216/
0011001110100000
0100110001010111
MD61
173304101/
0000101001010100
0110100100100101
MW42 (LSW)
26917/0000101001010100
0110100100100101
MD61
173304101/
0000101001010100
0110100100100101
MB43 (MSW)
2644/
0000101001010100
0110100100100101
MD62
982644150/
0011101010010001
1111010110110110
MB44 (LSW)
62902/0011101010010001
1111010110110110
MD62
982644150/
0011101010010001
1111010110110110
MB45 (MSW)
14993/
0011101010010001
1111010110110110