49P11-843

Emerson SureSwitch™

PART NO. 

37-7295B

Replaces 37-7295A

1304

INSTALLATION INSTRUCTIONS

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE 
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY 
AND/OR PROPERTY DAMAGE.

 

 PRECAUTIONS

CONTENTS

Description .......................................................................

1

Precautions .......................................................................

1

Specifications

 ...................................................................

2

Mounting ..........................................................................

2

Quick Reference ................................................................... 2

Operation .........................................................................

3

Troubleshooting ...............................................................

3

Wiring Diagram .................................................................... 4

 

 DESCRIPTION

SureSwitch™ is an electronically-controlled relay that can be used 
to replace single and two-pole contactors commonly used in air 
conditioners, heat pumps and other applications. A patented switching 
algorithm reduces arcing between contacts, which nearly eliminates 
pitting and welding for a longer life. The switching mechanism is sealed 
to prevent intrusion from insects and other debris.  
SureSwitch also provides advanced features for HVAC troubleshooting 
and system reliability:

•  Line-Voltage Brownout Protection
•  Short Cycle Protection
•  Random Start Delay
•   Lifetime Cycle Count

SureSwitch is similar to a 

1

/

2

 pole 

contactor, in that only the 

compressor terminal 

C

 is switched. The compressor terminal 

R

 is 

connected by a shorting bar to line input 

L

1

, and is energized even 

when a call is not present.

Installation should be done by a qualified heating and air conditioning 

contractor or licensed electrician.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical codes and 
ordinances.
This control is a precision instrument, and should be handled carefully. 

Rough handling or distorting components could cause the control to 

malfunction.
Following installation or replacement, follow manufacturer's 
recommended installation/service instructions to ensure proper 
operation.

SureSwitch has no user serviceable parts. Replace as a unit. 

www.white-rodgers.com

www.emersonclimate.com

Operator: Save these instructions for future use!

Failure to comply with the following warnings could result 
in personal injury or property damage.

FIRE HAZARD

•  Do not exceed the specified voltage.
•  Replace existing control with exact model and dash 

number.

•  Protect the control from direct contact with water 

(dripping, spraying, rain, etc.).

•  If the control has been in direct contact with water, 

replace the control.

•  Label all wires before disconnection when servicing 

controls. Wiring errors can cause improper and 
dangerous operation.

•  Safety route and secure wiring after installation.

SHOCK HAZARD

•  Disconnect electric power before servicing.
•  Ensure proper earth grounding of appliance.
•  Ensure proper connection of line neutral and line hot 

wires.

•  Compressor output "R" is not switched and is 

energized at all times.

WARNING

!

Summary of Contents for White Rogers SureSwitch 49P11-843

Page 1: ...on should be done by a qualified heating and air conditioning contractor or licensed electrician Do not exceed the specification ratings All wiring must conform to local and national electrical codes and ordinances This control is a precision instrument and should be handled carefully Rough handling or distorting components could cause the control to malfunction Following installation or replaceme...

Page 2: ...ng plate has four mounting holes that match the typical mounting screw locations of a single or two pole contactor Secure the bottom mounting plate to the control box using the two self tapping screws provided 6 Replace the main housing on the mounting plate and secure by tightening all four housing captive screws Take care to avoid over tightening 7 Connect line and control voltage wiring Refer t...

Page 3: ...e disabled by setting the Delay dipswitch to the OFF position LINE VOLTAGE BROWNOUT PROTECTION Brownout protection will de energize the compressor and fan if line voltage drops below 180 VAC for more than four seconds during a call for compressor operation Compressor operation will not resume until line voltage returns to a minimum of 190VAC In addition SureSwitch will not attempt to start the com...

Page 4: ...rankcase Heater 2Wire Hardstart Kit optional FAN HERM COM Line voltage Low voltage Line voltage optional circuit Optional components Legend T1 Fan Run T2 Start Separate Capacitor Optional Fan Capacitor Fan Run Common Start Fan Separate Capacitor Optional Capacitor 49P11 843 SureSwitch 4 Wire Condenser Fans 3 Wire Condenser Fans The following wiring diagram is meant to represent typical installatio...

Page 5: ...on ou par un électricien agréé N excédez pas les spécifications du produit Tout le câblage doit respecter les codes et règlements locaux et nationaux de l électricité Ce thermostat est un instrument de précision et il doit être manipulé avec soin Une manipulation robuste ou la modification des composantes peuvent causer la défaillance du thermostat Après l installation ou le remplacement respectez...

Page 6: ...laque de montage du boîtier principal 5 Le bas de la plaque de montage est pourvu de quatre trous de montage qui correspondent à l emplacement typique des vis de montage pour un contacteur mono ou bipolaire Fixer le bas de la plaque de montage sur la boîte des commandes à l aide des deux vis autotaraudeuses fournies 6 Replacer le boîtier principal sur la plaque de montage et fixer le tout en serra...

Page 7: ...baisse de tension coupe le compresseur et le ventilateur lorsque la tension de ligne chute sous 180V c a pendant plus de quatre secondes alors que le système appelle au fonctionnement du compresseur Le compresseur ne redémarre pas tant que la tension n atteint pas au minimum 190V c a De plus le module SureSwitch ne tente pas de redémarrer le compresseur tant que la tension de ligne est inférieure ...

Page 8: ...cultatives Légende T1 Ventilateur Marche T2 Démarrage Condensateur du ventilateur Ventilateur Marche Neutre Démarrage Condensateur distinct facultatif 49P11 843 SureSwitch Ven lateurs de condensateur à 4 fils Ven lateurs de condensateur à 3 fils Condensateur du ventilateur Condensateur distinct facultatif Condensateur du ventilateur Condensateur distinct facultatif Condensateur du ventilateur Cond...

Page 9: ...cionado o por un electricista profesional No exceda los valores nominales especificados Todas las conexiones eléctricas deben cumplir con los códigos y reglamentaciones locales y nacionales Este control es un instrumento de precisión y debe manipularse con cuidado La manipulación descuidada o la distorsión de los componentes podrían hacer que el control no funcionara correctamente Una vez finaliza...

Page 10: ...taje tiene cuatro orificios de montaje que coinciden con las ubicaciones típicas de los tornillos de montaje de un contactor monopolar o bipolar Fije la placa de montaje inferior a la caja de control utilizando los dos tornillos autorroscantes suministrados 6 Vuelva a colocar la carcasa principal sobre la placa de montaje y fíjela ajustando los cuatro tornillos cautivos de la carcasa Evite ajustar...

Page 11: ...ONTRA CAÍDA DEVOLTAJE DE LÍNEA La protección contra caídas de voltaje desenergiza el compresor y el ventilador si el voltaje de línea cae por debajo de los 180VCA durante más de cuatro segundos durante una llamada de funcionamiento de compresor El funcionamiento del compresor no se reanudará hasta que el voltaje de línea vuelva a 190VCA como mínimo Además SureSwitch no intentará iniciar el compres...

Page 12: ...ERM COM Voltaje de línea Bajo voltaje Circuito opcional de voltaje de línea Componentes opcionales Leyenda T1 Ventilador T2 Arranque Capacitor del ventilador Ventilador Común Arranque Capacitor separado opcional 49P11 843 SureSwitch Ven ladores de condensador de 4 cables Ven ladores de condensador de 3 cables Capacitor del ventilador Funcio namiento Capacitor separado opcional Funcio namiento El s...

Reviews: