ABB Power T&D Company Inc.
Power Automation & Protection Division
Coral Springs, FL 33065
Instruction Leaflet
All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the
local ABB Power T&D Company Inc. representative should be contacted.
Printed in U.S.A
.
41-496.52D
Type SDG-1T, -2T, -4T
Static Ground Distance
Supersedes I.L. 41-496.52C, Dated January 1987
( | ) Denotes Changed Since Previous Issue
!
CAUTION
Before putting relays into service, remove
all blocking which may have been inserted
for the purpose of securing the parts dur-
ing shipment, make sure that all moving
parts operate freely, inspect the contacts
to see that they are clean and close prop-
erly, and operate the relay to check the set-
tings and electrical connections.
1.
APPLICATION
Type SDG-1T, 2T and 4T relays are single zone
ground distance relays used to detect faults on sub-
transmission or transmission lines. Table
I
shows the
particular application intended for each relay and the
components included.
The I
0
fault detector prevents potential circuit trouble
from causing immediate trip. The frequency verifier
should be utilized for all high speed trip applications
to avoid tripping on line energization or other condi-
tions that cause high frequency transients.
The phase-to-phase desensitizer is used to eliminate
a possible overreach on two-line-to-ground faults.
This circuit is needed for Zone1 applications. It is not
needed for overreaching applications. The nature of
the design is that the phase-to-phase desensitizer is
removed from service on settings S = 2 or S = 3.
The potential supply must be 4 wire Wye-grounded.
The broken delta voltage connection is provided inside
the relay.
Mutual compensation is not required with these relays.
With an 85% Zone1 setting and an extreme zero-
sequence mutual impedance, the relay will reliably
reach ground faults on at least 70% of the protected
line.
All three relays are equipped with normally open out-
put contacts and ICS’s for indicating trip coil current
flow. In addition the SDG-4T has a normally-closed
contact for “contact-opening-carrier start”.
Table 1
Relay
I0
Fault
Det
Freq.
Verifier
Phase-to-
Phase
Desensitizer
(Note 1)
Application
SDG-1T
SDG-2T
SDG-4T
X
–
–
X
X
–
X
X
–
Zone-1 or Zone-2
Zone-1 or Zone-2
Blocking
Carrier Start
Note 1:
For time delayed trip disconnect 2Ø-G circuit. A switch
is provided for this function in the SDG-1T.
Effective:
December 1996
Summary of Contents for SDG-1T
Page 11: ...I L 41 496 52D 11 ...
Page 13: ...I L 41 496 52D 13 ...
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 37: ......
Page 43: ......
Page 47: ......
Page 48: ......
Page 49: ......