HY, year time switch
267
02/16 MN05013001Z EN
Total result corresponding to the channel configurations and
behaviour of contact Q1 in this example:
The time switch switches on at 00:00 on 3 May and stays on
until 00:00 on 26 May.
In June, July, August, September, October, the time switch
will switch on at 00:00 on day 2 of the month and switch off
at 00:00 on day 18.
In November and December, the time switch will switch on
at 00:00 on the second of the month and switch off until
00:00 on the 18th. The following note explains this
switching behaviour.
HY01 C
+
>ON 03.05.--
>OFF 25.10.--
HY01 D
+
>ON 02.06.--
>OFF 17.12.--
h
Switching behaviour of channels parameterized with over-
laps:
If parameterised ranges overlap, the year time switch
switches the contact on with the first detected ON, irre-
spective of which channel supplies this ON signal. In the
same way, the year time switch switches the contact off
with the first detected OFF, irrespective of whether
another channel still supplies the ON signal.