The first circuit diagram
105
02/16 MN05013001Z EN
Test using the power flow display
A easySafety device enables you to check the power flow in
RUN mode. While the device is processing the circuit
diagram in RUN mode, you can use the integrated power
flow display to check this.
X
Change to the circuit diagram display and press
pushbutton S1.
The relay picks up and the easySafety displays the power
flow with a double line.
Figure 42:
Power flow display: Inputs
IS1
and
IS2
are closed,
relay
QS1
has picked up
= Visible area
X
Press pushbutton actuator S2, that has been connected as
a break contact.
The power flow is interrupted and relay Q1 drops out.
Figure 43:
Power flow display: Input
IS01
is closed, input
IS02
is open, relay
QS1
has dropped out
= Visible area
X
Press ESC to return to the Status display.
IS01====IS02===================
Ä
QS01
L: 1 C:1 RUN
IS01====IS02-------------------
Ä
QS01
L: 1 C:1 RUN
h
The standard circuit diagram does not have to be completed in
its entirety so that it is possible to test parts of it.
The easySafety device simply ignores any incomplete standard
wiring that is not yet working and only uses the finished wiring.