ZM, zero (standstill) moni-
toring
511
02/16 MN05013001Z EN
Figure 270:
Wiring of input coils
You can associate the enabling contact ZM..QS directly for
further processing, for example:
L
Figure 271:
Wiring of the enable contact to a safety marker for
further processing in the safety circuit diagram
Parameters
When using the function block in the circuit diagram for the
first time, use OK to automatically enter the general display
of function block parameters, as shown in the figure on the
left. Enter the function block settings here. The display
contains the following elements:
The parameters consist of the following:
IS03---------------------------
Ä
ZM01RE
OS01Q1-------------------------
Ä
ZM01SA
ZM01QS---------------------------
Ä
MS01
i
Warning!
When using function block ZM, make sure that it enables
the dangerous motion through its contact ZM..QS.
Keep in mind that the easySafety device can change into
its safe state when the dangerous motion is already
enabled before the easySafety device is switched on.
ZM01 NEN MST *
*** ***
>FR
2
Hz
ZM01
Function block: Zero speed monitoring, No. 01
NEN
Enable: none required
MST
Operating mode: Manual start
>FR
Maximum rotation frequency: 2 Hz
Summary of Contents for easySafety