![Eaton easySafety Manual Download Page 665](http://html1.mh-extra.com/html/eaton/easysafety/easysafety_manual_3958374665.webp)
Technical data
661
02/16 MN05013001Z EN
IEC 61508
PFD
Relay output
K1 + K2
x
c
2
+ K3
x
c
K1 = 5.1 x 10
-5
K2 = 1.5 x 10
-6
K3 = 2.4 x 10
-5
c = operating frequency
Transistor output
5.29 x 10
-5
PFH
1/h
Relay output
K1 + K2
x
c
2
+ K3
x
c
K1 = 6.4 x 10
-10
K2 = 2.6 x 10
-11
K3 = 3.2 x 10
-10
c = operating frequency
Transistor output
6.57 x 10
-10
1-channel architecture/HFT 0
EN ISO 13849-1
MTTF
d
Years
Relay output
K1 = 1.7 x 10
-3
K2 = 1.2 x 10
-3
c = operating frequency
Transistor output
315
T10
d
Years
10 % von MTTF
d
ES4P…
1
K1 + K2
x
c