Working with contacts and
relays
145
02/16 MN05013001Z EN
Coil functions
You can set the coil function to determine the switching
behaviour of relay coils. The following coil functions are
assigned to all coils:
Table 10: Coil function
easySafety
display
Coil function
Example
a
Page
Ä
Contactor function
Ä
QS01,
Ä
D02,
Ä
S04,
Ä
:01,
Ä
M07,..
ä
Impulse relay function
ä
QS03,
ä
M04,
ä
D08,
ä
S07,
ä
:01,..
S
Set
SQ08,SM02,SD03,SS04..
R
Reset
RQ04,RM05,RD07,RS03..
Å
Contactor function with
negated result
Å
QS04,
Å
M96..
È
Cycle pulse with rising edge
È
M01..
è
Cycle pulse on falling edge
è
M42..
h
The function block coil functions that can be used are
described with the function blocks.
h
With non-retentive coil functions such as
Ä
(contactor),
Å
(negated contactor),
È
,
è
(rising and falling edge
evaluation): Each coil must only be used once. The last coil
in the circuit diagram determines the state of the relay.
Exception: When working with jumps, the same coil can
be used twice.
Retentive coil functions such as
S
,
R
,
ä
can be used
several times.