SR, shift register
301
02/16 MN05013001Z EN
e
Coil SR..FD: Data bit forwards.
f
Coil SR..BD: Data bit backwards.
g
Input SR..I1: Input value forwards.
h
Input SR..I2: Input value backwards.
i
Contact SR..Q1 to SR..Q8: Close, as long as your register values
are 1.
j
Outputs SR..D1 to SR..D8: Register values 1 to 8 of the shift
register.
Wiring of the function block
In BIT mode you integrate the shift register function block in
the standard circuit diagram with its coils and contacts:
Figure 143: BIT mode, wiring the function block coils
The function block coils are switched by markers.
Figure 144: BIT mode, wiring the function block contacts
The contacts of the function block are connected with
markers.
In DW mode you only integrate the coils in the standard
circuit diagram:
M 10--------------------------
Ä
SR01EN
M 11--------------------------
Ä
SR01FD
M 12--------------------------
Ä
SR01FP
M 13--------------------------
Ä
SR01BD
M 14--------------------------
Ä
SR01BP
M 15--------------------------
Ä
SR01RE
SR01Q1------------------------
Ä
M1
SR01Q2------------------------
Ä
M2
SR01Q3------------------------
Ä
M3
SR01Q4------------------------
Ä
M4
SR01Q5------------------------
Ä
M5
SR01Q6------------------------
Ä
M6
SR01Q7------------------------
Ä
M7
SR01Q8------------------------
Ä
M8