Technical data
665
02/16 MN05013001Z EN
Electromagnetic compatibility (EMC) according to IEC 61000-4, IEC 61000-6-2
Electrostatic discharge (ESD),
to IEC 61000-4-2
Air discharge
kV
8
Contact discharge
kV
6
Electromagnetic fields (RFI),
to IEC 61000-4-3
V/m
20
Radio interference suppres-
sion
EN
55011
Class B,
Burst,
to IEC 61000-4-4
Power lines
kV
4
Signal lines
kV
4
Power pulses (surge), to IEC
61000-4-5
kV
1 (supply cables inputs, symmetrical)
2 (semi-conductor outputs, symmetrical)
radiated RFI,
to IEC 61000-4-6
V
20
Increased EMV requirements to IEC 62061 for safety-related functions.
Electrostatic discharge (ESD),
to IEC 61000-4-2
Air discharge
kV
15
Contact discharge
kV
8
Electromagnetic fields (RFI),
to IEC 61000-4-3
V/m
30
Burst,
to IEC 61000-4-4
Power lines
kV
4
Signal lines
kV
4
Power pulses (surge), to IEC
62061
kV
2 (supply cables inputs, symmetrical)
4 (semi-conductor outputs, symmetrical)
ES4P…