    PPM - 05 PRIORITY  RELAY 

INSTRUCTION MANUAL

Zakład Mechaniki i Elektroniki 

ZAMEL 

sp.j.

J.W. Dzida, K. Łodzińska

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04

www.zamelcet.com, 

e-mail:

 [email protected]

FEATURES

TECHNICAL DATA

DESCRIPTION

APPERANCE

PPM - 05

Power terminals:

L, N

Rated voltage: 230 V~

Rated voltage tolerance: -15 ÷ +10 %

Rated frequency: 50 / 60Hz

Rated current:  34 mA

Measure termianals: 1, 2

Current threshold adjustment:

0,5 ÷ 5 A (hysteresis ~5%) - for PPM-05/5

0,8 ÷ 8 A (hysteresis. ~5%) - for PPM-05/8

1,6 ÷ 16 A (hysteresis ~5%) - for PPM-05/16

Current measure tolerance: ≤ 20%

OFF-time delay: 0,5 ÷ 20 s

Supply voltage indicator: green LED

Current threshold exceed indicator:

red LED

Relay contacts parameters: 1NO/NC - 16 A / 250 V AC1 4000 VA

Connection terminals quantity: 7

Connection wire section: 0,2 ÷ 2,5 mm

2

Operating temperature: -20 ÷ +60 

o

C

Operating position: optional

Casing fastening: TH 35 rail (according to PN-EN 60715)

Casing IP: IP20 (PN-EN 60529)

Protection class:

II

Overvoltage category:

II

Pollution level: 2

Dimensions: single-module (17,5 mm) 90x17,5x66 mm

Weight: 88 g

Standard conformity: PN-EN 60730-1; PN-EN 60730-2-1

PN-EN 61000-4-2,3,4,5,6,11

ی  Both  priority  and  non-priority  circuits 

control,

ی 

Three product versions, in dependen-

ce of the current level

,

ی  Power supply indicator,
ی  Current threshold indicator,
ی  Continuous delay time adjustment,
ی  Continuous  current  threshold  adjust

-

ment,

ی  Measure circuit separated voltaic,
ی  Relay voltage output, changeover con

-

tact, maximum load 16 A,

ی  Mounted on TH 35 rail.

The PPM-05 priority relay is designed 

for current control in priority and / or non-

priority load circuits. When the current mea

-

sured on measure terminals (1, 2) exceeds 

the preset value, the device will switch-OFF 

a non-priority receiver with the preset delay 

time. The current threshold and delay time 

may be adjusted by the user. It is possible to 

protect the electrical network against over

-

loads by means of the relay, but the device 

may  not  replace  a  current-limiting  circuit-

breaker.

Rela

y

 

o

u

t

pu

t

 

Suppl

y

 

vo

l

t

a

g

e i

n

di

c

a

to

r

P

o

wer 

t

ermi

n

al 

(

L

)

P

o

wer 

t

ermi

n

al 

(

N

)

Measure lead

terminals  (1, 2)

terminals (11, 12, 14)

Current threshold setting

Current threshold exceed
indicator
OFF-time delay
setting

The  timer  should  be 
connected  to  a  single-
phase  system  accordin

-

gly to current standards.
The  device  connections 
will be described  in this 

manual.  Only  qualified  electricians  are 
allowed  to assembly, connect and ad

-

just the timer. It is necessary to read this 
manual  before  the  timer  mounting.  Do 
not disassembly the timer casing or you 
will lose any warranty rights and expo

-

se yourself to the electric shock hazard. 
Before  mounting  operation  make  sure 
of  disconnecting  the  connection  wires  
from  the  electric  network.    The  timer 
should  be  carried,  stored  and  used  in 
an appropriate way.  Do not mount the 
timer  in  case  of  any  device  parts  lack, 
damage or deformation. In case of mal

-

function please notify the manufacturer.

CAUTION

Reviews: