Commissioning NET stations
543
02/16 MN05013001Z EN
Checking the functionality of the NET
You can make a visual check the functionality of the NET by
means of the NET LED and in the circuit diagram via
diagnostics bit ID01-ID08.
Table 25: Checking the functionality of the NET using the NET LED
Status of the NET
LED
Meaning
Off
NET not operational, fault in
configuration
Continuous light
NET station fault, possible causes:
• Net is initialized and at least one
station has not been detected. Check
the plug-in connections.
• You have modified the NET ID or baud
rate for at least one station after the
configuration has been completed.
Change the configuration.
• On a NET station you have changed
the configuration
and thus deleted its
NET configuration,
Reconfigure the NET via station 1.
• You have expanded an existing NET
station and replaced it with a new
device which cannot be assigned
parameters.
Flashing
NET operating fault-free