74
02/16 MN05013001Z EN
Local standard expansion device
For non-safety expansion, the local expansion unit is
positioned directly next to the basic unit.
X
Connect the easy expansion with the EASY-LIN-DS
connection plug.
Figure 30:
Connecting local expansions with easySafety
EASY-LINK-DS
EASY6..-..-RE..
EASY6..-..-TE..
EASY2…
ES4P-221-....
j
Danger!
The following electrical isolation is implemented between
the ES4P-221-…basic device and the expansion device
(isolation always in local connection of expansion device):
• Basic isolation 400 V AC (+10 %)
• Safe isolation 240 V AC (+10 %)
Units may be destroyed if the value 400 V AC +10 % is
exceeded, and may cause the malfunction of the entire
system or machine!
h
Basic unit and expansion unit can be provided with
different DC power supplies.