Description of the NET-
PARAMETERs
563
02/16 MN05013001Z EN
REMOTE RUN
(operating mode change according to the operating mode of
the NET station with NET ID 1)
Factory setting REMOTE RUN = On
REMOTE RUN must be activated on NET stations with NET
ID 2 - 8 which are required to automatically follow the
operating mode change of the NET station with NET ID 1.
h
If you are currently setting the station with NET ID 1, the
REMOTE RUN function is therefore not required and is not
available here.
j
Danger!
Ensure that the automatic starting of easySafety will not
cause the unwanted starting of machines and plants.
h
NET stations with a circuit diagram and a display only
follow the operating mode change if the status display or
a text is showing in the display on the device.