SE, Start element
459
02/16 MN05013001Z EN
Evaluation only in the standard circuit diagram with the diag-
nostics function block DG.
Wiring of the function block
The function block uses various different coils and contacts.
The coils SE..I1 and SE..RE can be addressed via any possible
association. Example of a start element function block:
Figure 235:
Wiring of input coils
The SE..QS function block can likewise be used in the safety
circuit diagram, for example:
L
Figure 236:
Wiring of the enable contact
Parameters
When using the function block in the circuit diagram for the
first time, use OK to automatically enter the general display
of function block parameters, as shown in the figure on the
left. Enter the function block settings here. The display
contains the following elements:
The parameters consist of the following:
TS01QS-------------------------
Ä
SE01I1
IS02----MS01-------------------
Ä
SE01RE
SE01QS---MS04-------------------
Ä
TS02SA
SE01 NEN MST *
*** ***
SE01
Function block: Start element, number 01
NEN
Enable: none required
MST
Operating mode: Manual start