PS220 Configuration & Operation Guide
PS220 136
Functions &
Features
Critical Speed Windows
The PumpSmart PS220 can be configured to bypass operating speed windows to avoid
resonance frequencies that may be encountered when running a pumping system. Refer to the
pump manufacturer to determine if the pump being controlled has a critical speed within the
defined operating speed range (between 30.11 MIN SPEED and 30.12 MAX SPEED).
Parameter
Name
Value/Range
Note(s)
22.51
CRITICAL SPEED FUNC
0-1
0-Disables [default]
0000 will display as default
Bit 0 will need to be
changed to a 1 to Enable
22.52
CRITICAL SPEED 1 LOW
-30000 to +30000
0 [default]
Refer to the pump
manufacturer for critical
speeds or determine these
speeds during commissioning
of the system.
22.53
CRITICAL SPEED 1 HIGH
-30000 to +30000
0 [default]]
22.54
CRITICAL SPEED 2 LOW
-30000 to +30000
0 [default]
22.55
CRITICAL SPEED 2 HIGH
-30000 to +30000
0 [default]
22.56
CRITICAL SPEED 3 LOW
-30000 to +30000
0 [default]
22.57
CRITICAL SPEED 3 HIGH
-30000 to +30000
0 [default]
NOTE: This function will not allow the operating speed to be maintained within the bands
selected and should not be used with any PS220 PROCESS CONTROL MODES.
Diode Test
A Diode test may need to be performed when drive faults occurred. Typically these are a result
of incoming power problems, or they may be the result of a fault Input Bridge. This procedure
will show how measure and document readings necessary to determine a remedy.
1. Take readings of the VFD input diode bridge.
• Make sure the mains power supply (460 VAC) is OFF.
• Set the Digital MultiMeter Meter to be in the diode mode
• Place one of the leads on the UDC+ terminal and the second one on one of the input
phases (L1, L2, and L3) per the table below. Document the readings in the table below.
• Repeat the test for the other two input phases and note the reading.
• Switch the DMM leads now and repeat the test. Document the readings in the table below.
• Typical readings will show values. Any reading that shows “OL” will be problematic.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...