PS220 Configuration & Operation Guide
PS220 122
Functions &
Features
ALARM AND CONTROL
An integral part of the core functionality of the PS220 is the ability for it to identify pumping system problems, provide
a notification, determine the possible causes, and to allow the customer to predefine and implement corrective action
measures automatically. The Alarm and Control Function allows for the predefining of these corrective actions. The
actions listed below are also an integral part of the Pump Protections Wizards.
For Basic Pump Protection:
The PumpSmart PS220 will either:
A. Issue a warning message signifying the event9s), and either run at minimum speed or stop. It can be configured to
automatically re-start after a delay period and then run again to try to maintain the process setpoint. It can be con-
figured to follow this routine a set number of times before a hard Fault is issued. The Fault will have to be reset, and
manually restarted.
B. A hard Fault is issued, and it will stop. The fault message will be displayed, and it will have to be reset, and manually
restarted.
For Minimum Flow Protection:
The PumpSmart PS220 will indicate that the pump is running at or below minimum flow with a message “Min Flow
Warning”. After the response delay time has expired. The event will be stored in the Event Log. The PS220 will then re-
spond based on the Protections Options. If and when a hard fault occurs it will display the message “Min Flow Fault”.
The PS220 will have to be reset and manually restarted. Please refer to the sections “Protection Options” and “Fault
Tracing” in this manual.
For Secondary Protection:
The PumpSmart PS220 will indicate a “Secondary Protect A, (B)” warning message, after the response delay time has
expired. The event will be stored in the Event Log. The PS220 will then respond based on the Protections Options.
With every occurrence, the event(s) are automatically logged in the PS220’s Event Log, which are Date and Time
stamped for historical analysis.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...