PS220 Configuration & Operation Guide
PS220 252
Fault T
racing
have been added to piping.
•
Check discharge piping static height compared to TDH
output of the pump.
E211
CONDITION 2 LO
WARNING
Warning Only
The signal level for Condition 2
fallen below the 80. 12 COND 2
WRN LIM LO.
•
Investigate cause of condition
•
Check parameter settings of 80.12
E212
PIPE CLEAN TIME OUT
Warning Only
Unable to complete the pipe
clean sequence.
•
Check parameter settings of 83.22 and 83.23
•
Verify that the PS220 is not current limited and is able
to reach maximum speed set up in 30.12
•
Verify that another warning or fault is not active. This
can be seen in the event log.
E213
SPEED OVERRIDE
Warning Only
The PS220 Speed Override
function is active
•
The Speed Override function is running. Waring message
only. Check that Speed Override Pump protection is
active (79.04) if required to protect the pump.
E214
CONDITION 2 HI WARNING
Warning Only
The signal level for Condition 1
has exceeded the
80.11 COND 2 WRN LIM HI.
•
Investigate cause of condition
•
Check parameter settings of 80.06
E215
PUMP CLEANING
RUNNING
Warning Only
Pump clean sequence is being
executed
•
Check parameter 83.01 and 83.02 to verify that the
cleaning sequence is executing as intended.
E216
PUMP CLEANING (RT)
RUNNING
Warning Only
The Pump Cleaning sequence
has re-executed. It did not
unclog in the previous try.
•
PS220 try will continue to run the sequence until the
pump is unclogged. If the number of cycles set up in
83.06 has exceeded and the pump is still clogged, the
PS220 will respond based on parameter 83.18.
E217
PUMP CLEANING
WARNING
Pump clean sequence is being
executed
•
Check parameter 83.01 and 83.02 to verify that the
cleaning sequence is executing as intended.
E218
PIPE CLEANING (RT)
RUNNING
Warning Only
The Pipe Clean Sequence has
initiated an automatic retry.
Warning message only. No action is necessary. Issue a
stop command to end the Pump Cleaning Sequence
completely.
E219
TOTAL SYSTEM FLOW
COMPLETED
Warning Only
The pump has completed
pumping the total volume set in
parameter 84.01.
•
The flow totalizing function is setup by parameters
84.01and 84.02.
•
Verify that the pumped volumes are based on the
above settings ( within the stated Ps220’s published
accuracy limits)
E220
COND 2 HI ALARM
Warning only
The signal level for Condition 2
has exceeded the
80.14 COND 2 ALAMR LIM HI.
•
Investigate cause of condition
•
Check parameter settings of 80.13 and 80.14
E221
CONDITION SLEEP
Warning Only
A Condition 1 or Condition 2
value exceeded the alarm limits,
and the Condition Sleep
Function is active.
•
Investigate cause of condition
•
Check parameter settings of 80.0,7 80.08,80.09,
80.13, 80.14 and 80.15
E222
COND 2 LO ALARM
Warning Only
The signal level for Condition 2
has fallen below 80.15 COND 1
ALAMRM LIM LO.
•
Investigate cause of condition
•
Check parameter settings of 80.13 and 80.15
E223
PID LOW DEMAND
Warning Only
The PS220 requires operating at
a speed below minimum speed
to maintain the set- point.
•
Check for reference not set to 0
•
Minimum speed 30.11 is set to high for the
application. The Pump may be oversized for the
system.
•
Check that Sleep Mode (75.03) is not set to disabled.
•
Check 79.16 is set to match 75.03
E224
START DELAY ACTIVE
Warning Only
Start delay has been
enabled.
•
No action required.
•
Once delay period is complete the pump will start
running.
E225
PRIMING ON
Warning Only
Pump is running the priming
function. It will run at full speed
with all logic and protection
turned off internally.
Warning only. It will run every time the start is received.
E226
STAGE TIMEOUT Alarm
Warning Only
The stage requested did occur. •
Re issue a start command on this pump
•
Cycle the power to the drive.
E21A
BYPASS VALVE OPEN
Warning Only
The PS220’s minimum flow
bypass valve control has
triggered the signal for a
relay to open a bypass
valve.
•
Warning message only.
•
NOTE: When the bypass closes there will not be a
message stating this.
E21B
PIPE CLEAN RUNNING
Warning Only
The PS220 is executing a pipe
clean sequence.
•
Verify that the sequence if operating based on
parameter settings 83.21, 83.22 & 83.23
E21C
PIPE FILL RUNNING
Warning Only
The PS220 Pipe-Fill function is
running
•
Warning only. No action required
E21D
PIPE FILL
The PS220 Pipe-Fill function is
running
Warning only. No action required
E21E
COND 1 HI ALARM
Warning Only
The signal level for Condition
1 has exceeded 80.08 COND
1 ALAMRM LIM HI
•
Investigate cause of condition
•
Check parameter settings of 80.07 and 80.08
E21F
COND 1 LO ALARM
Warning only
The signal level for Condition 1
has fallen below 80.09 COND 1
ALAMRM LIM LO.
•
Investigate cause of condition
•
Check parameter settings of 80.07 and 80.09
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...