PS220 Configuration & Operation Guide
131 PS220
Function & F
eatures
GROUP 80
CONDITION MONITORING
DESCRIPTION
80.01
CONDITION STATUS
A 1 indicates the condition is active
BIT
FUNCTION DESCRIPTION
0
Enabled
1
Cond1 High Alarm
2
Cond1 High Warning
3
Cond1 Low Warning
4
Cond1 Low Alarm
5
Cond2 High Alarm
6
Cond2 High Warning
7
Cond2 Low Warning
8
Cond 2 Low Alarm
13
Sleep Active
14
Min Speed Active
80.04
COND 1 SOURCE
None [Default]
Flow Actual
Pressure Actual
Level Actual
Speed
Torque
Power
Current
Temperature
Actual
SmartFlow
PROC TRANS 1
PROC TRANS 2
Select the source of the signal to be monitored. The
source can either be from an external transmitter wired
to an available analog input or it can be an internal
signal as selected by the parameter number.
80.05
COND 1 WRN LIM HI
-10000 to +10000
0 [default]
The high value of the warning limit. A warning
occurs if the monitored signal rises above this
value for longer than the response delay
Inactive if set to 0.
80.06
COND 1 WRN LIM LO
-10000 to +10000
0 [default]
The low value of the warning limit. A warning
occurs if the monitored signal drops below this
value for longer than the response delay. Inactive if
set to 0.
80.07
COND 1 ALARM
DISABLED [default]
Protection is inactive.
ALARM ONLY
Selecting ALARM ONLY will issue a Keypad
message showing that an ALRM LIM HI or ALRM LIM
LO condition is detected. No further action is
taken.
MIN SPD
Selecting MIN SPD will issue a Keypad message
showing that an ALRM LIM HI or ALRM LIM LO
condition is detected and will drop to MIN SPEED.
If the alarm does not reset itself after the MIN SPD
STP DLY the PS220 will fault.
SLEEP
The PS220 will shut down and go into a sleep mode
if an ALRM LIM HI or ALRM LIM LO condition is
detected. It will “wake up” according to the value
in 80.22.
FAULT
The PS220 faults if an ALRM LIM HI or ALRM LIM LO
condition is detected. A Keypad notice is issued
80.08
COND 1 ALRM LIM HI
-10000 to +10000
0 [default]
The high value of the alarm limit. An alarm occurs if the
monitored signal rises above this value for longer
than the condition response delay (par 80.16).
Inactive if set to 0.
80.09
COND 1 ALRM LIM LO
-10000 to +10000
0 [default]
The low value of the alarm limit. An alarm occurs if the
monitored signal drops below this value for longer
than the response delay (par 80.16). Inactive if set
to 0.
80.10
COND 2 SOURCE
None [Default]
Flow Actual
Pressure Actual
Level Actual
Speed
Torque
Power
Current
Temperature Actual
SmartFlow
PROC TRANS 1
PROC TRANS 2
Select the source of the signal to be monitored.
The source can either be from an external transmitter
wired to an available analog input or it can be an
internal signal as selected by the parameter
number.
80.11
COND 2 WRN LIM HI
-10000 to +10000
0 [default]
The high value of the warning limit. A warning occurs
if the monitored signal rises above this value for
longer than the response delay (par 80.16). Inactive
if set to 0.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...