PS220 Configuration & Operation Guide
PS220 236
Functions &
Features
The test can be done as follows:
1. Switch to “LOCAL” Keypad Control.
2. Start the Pump by pressing the Green Start Button.
3. Set the Speed Reference to Max Speed and let the pump run to full speed. Check and validate that the pump
is pumping with a “normal level” in the sump, or the suction side tank and it is maintaining a stable flow.
4. View/Record the value of Parameter 1 .10 MOTOR TORQUE in %. Multiply this value by 1.2. The factor 1.2
corresponds to the expected increased torque that can be expected when a clog may occur. Use this calculated
value when you configure parameter 83.03 TORQUE REQ.
5. Stop the PS220 with the Red Stop Button.
6. Switch back to REMOTE control.
The following steps will be followed to configure the Pump Cleaning Sequence. Refer to the description of each
parameter listed below for the functional description of each parameter.
1. Configure how the Pump Cleaning Sequence executes, Manually or Automatically
2. Configure what triggers the Execution of the Pump Cleaning Sequence when PS220 is configure for step 1.
(Automatic operation)
3. Configure the Torque Request Value above normal Torque for executing the PCS.
4. Configure the proof time before executing the PCS once the request torque threshold is met.
5. Configure the time of the day to execute the PCS.
6. Configure the maximum number of cycles the PCS can execute.
7. Configure the forward running speed during the PCS.
8. Configure the forward speed run time during the PCS.
9. Configure the forward run acceleration rate during the PCS.
10. Configure the forward run deceleration rate during the PCS.
11. Configure the time pause before reverse rotation begins during the PCS.
12. Configure the reverse run speed during the PCS.
13. Configure the reverse run time during the PCS.
14. Configure the Reverse Run Acceleration rate during the PCS.
15. Configure the Reverse Run Deceleration rate during the PCS.
16. Configure the maximum time the PCS is allowed to complete a full sequence.
17. Configure the maximum number of complete sequences the PCS is allowed to run.
18. Configure the Sequence Exceeded Reaction when the PCS does not reduce the torque to acceptable levels.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...