PS220 Configuration & Operation Guide
227 PS220
Function & F
eatures
2: H-O-A DI1, 2 DI5
This is a commonly requested External Switch Combination used on the PS220
Refer to the diagram below.
Functionality:
“Auto Control” from two external locations.
External Location 1:
DI1 is assigned to “Auto”
External Location 2:
DI5 is assigned to “Auto”.
This combination requires a pre-assigned switch
using Digital Input 3 (DI3) to switch between these
2 Auto Choices. DI3 High selects Auto DI1, DI3 Low
selects Auto DI5.
DI2 is assigned to Hand or “Speed Override”
All switches are normally open
The table below lists all the choices that can be configured for the start and stop method on the PS220. The Digital Inputs
assignments are automatically configured when using the PS220 Basic Setup Configuration Wizard for this function.
Parameter Name
Value/Range
Notes
74.01
START/STOP
KEYPAD [default]
Start /Stop controlled via the PS220 Keypad
2 WIRE DI1
Control at one external location via 2-Wire switch assigned to DI1. DI1 is normally open.
3W DI1P,2P
Control at one external location. Pulse start assigned to DI1 and pulse stop assigned to
DI2. DI2 will be “normally closed”
HOA DI1,2
Control Used for Hand-Off-Auto. DI1is assigned to Auto; DI2 is assigned to Hand (Speed
Override).Both are normally open.
HOA DI1,2 – DI5
Control at two external locations.
EXT1: Hand-Off-Auto. DI1 is assigned to Auto, DI2 is assigned to Hand(Speed Over)
EXT2: Auto. 2-Wire switch is assigned to DI5.
This combination requires a preassigned switch (DI3) to switch between these 2 choices.
All switches are normally open
DI1P,2P- DI5
Control at two external locations.
EXT1: Pulse start assigned to DI1 and pulse stop assigned to DI2. DI1 is normally open
and Di2 is normally closed.
EXT2: Auto is a 2-Wire start/stop switch assigned to DI5. Normally open.
This requires a preassigned switch (DI3) to switch between these 2 choices.
HOA DI1,2 –FB
Control at two external locations.
EXT1: Hand-Off-Auto. DI1 is assigned to Auto, DI2 is assigned to Hand (Speed Override).
EXT2: Fieldbus is the second control location.
This requires a preassigned switch (DI3) to switch between these choices. All switches
are Normally open
2W DI1 – 2W DI5
Control at two external locations.
EXT1: 2-Wire assigned to DI1.
EXT2: 2-Wire switch at DI5.
This requires a preassigned switch (DI3) to switch between these choices.
All switches are “normally open”
FIELDBUS
Start via Fieldbus control word. External control location 1 only.
DI1P,2P - FB
Control at two external locations. EXT1: 3-Wire pulse start DI1 and pulse stop DI2. EXT2:
Fieldbus control word. This requires a preassigned switch (DI3) to switch between these
choices.Di1 and di3 are normally open. DI2 is normally closed.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...