PS220 Configuration & Operation Guide
PS220 168
Functions &
Features
Multipump Menu Tree
Below is the chronologic list of steps that the PumpSmart PS220 Multi-
pump Wizard follow during the configuration of the system.
The Section in the Wizards has each and every screen shot shown for easy
step by step instructions.
This functionality can be configured with the PumpSmart PS220 Config-
uration Wizard. To access this Wizard from the Home Screen, follow the
path: Menu>PS220 Configuration>Multipump>
NOTE: When Configuring Multiple Pumps to be used in your system you
will need to follow these steps on each PS220 installed. However, all of
the settings will be identical except for step 2 below.
1. Configure the Multipump Mode
“Synchronous” enables the Multipump Functionality.
2. Configure the Pump Address (1-6)
NOTES:
1. This Pump address MUST entered in same fashion as the PS220’s are
wired with the D2D connections. Refer to the wiring diagrams in this
manual. They must be wired in the 1-2-3-4-5-6 ring configuration.
2. Configuring the remaining Pumps will only require this number to be
changed to 2, 3, 4, 5 or 6.
3. Configure the Lead/Lag Switch Hours
The default value is 48 Hours
4. Configure the Value Increase and Decrease Values:
The default values are 5%
5. Configure the Stage and Destage Method
The default value is SPEED/Torque. The options is for Process Value,
typically used for Level Control applications. The Torque selection will
require the Miscellaneous Wizard to be run for Torque control
6. Configure the STAGE PROOF TIME:
The default value is 20 seconds.
7. Configure the DESTAGE PROOF TIME
The default value is 20 seconds.
8. Configure the MIN PUMPS ON
The default is 1
9. Configure MAX PUMPS ON
The default value is 4.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...