PS220 Configuration & Operation Guide
59 PS220
Pump & VFD Protection
4. Configure the Minimum Flow Value
1. “ARROW RIGHT” to change
2. “ARROWS” to change value
3. “Save”
4. “ARROW DOWN”
5. Configure the Response to Dry Run.
The choices are:
1. Disabled (Default)
The PumpSmart PS220 will continue to run. There will not be any indication of this event.
2. Fault.
The PumpSmart PS220 will fault off with the message “Dry Run Fault” after the Response Delay
time has expired. It will be stored in the event log. This fault is not an Auto-resettable fault. The
fault will have to be reset, and the drive issued a start command again. Please refer to the sec-
tion “Fault Tracing” in this manual.
3. Warning.
The PumpSmart PS220 will continue to run and will indicate a message “Dry Run Warning” after the
Response Delay time has expired. It will be stored in the event log. No other action will be taken.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...