PS220 Configuration & Operation Guide
259 PS220
Fault T
racing
Each Fault message on the keypad displays the fault name as well as and unique code. The faults are
listed in the ascending order of their fault codes. A fault will cause the drive the stop the pump.
CODE
(HEX)
WARNING
CAUSE
WHAT TO DO
7084
Panel/PC tool version
conflict
The current version of the
control panel and/or PC tool
does not support a function.
(For example, older panel
versions cannot be used as a
source of external reference.)
•
Update control panel and/or PC tool. Contact your local
ABB representative if necessary.
7121
Motor stall Programmable
fault: 31.24 Stall function
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
•
Check motor load and drive ratings. Check fault function
parameters.
7310
Overspeed
Motor is turning faster than
highest allowed speed due to
incorrectly set minimum/
maximum speed.
•
Check minimum/maximum speed settings, parameters
30.11 Minimum speed and 30.12 Maximum speed.
•
Check the motor disconnect to make sure is closed
Incorrect estimated speed.
•
Check the status of motor current measurement.
•
Perform a Normal, Advanced or Advanced Standstill ID
run instead of, for example, a Reduced or Standstill ID
run. See parameter 99.13 ID run requested.
7582
MF Comm loss
Programmable fault: 60.09
M/F Comm loss function
Master/follower
communication is lost.
•
Check cables between Master and follower
•
Check node address and other setup parameters in
Multipump wizard
•
Replace cables.
•
Drive is in Local in Multipump
80A0 AI supervision
Programmable fault:
12.03 AI supervision
function
An analog signal is outside the
limits specified for the analog
input.
•
Check signal level at the analog input.
•
Check the wiring connected to the input.
•
Check the minimum and maximum limits of the input in
parameter group 12 Standard AI.
FB11
Memory unit missing
No memory unit is attached to
the control unit.
•
Power down the control unit.
•
Check that the memory unit is properly inserted into the
control unit.
The memory unit attached to
the control unit is empty.
•
Power down the control unit. Attach a memory unit
(with the appropriate firmware) to the control unit.
FB12
Memory unit incompatible The memory unit attached
to the control unit is
incompatible.
•
Power down the control unit. Attach a compatible
memory unit.
FB13
Memory unit FW
incompatible
The firmware on the attached
memory unit is incompatible
with the drive.
•
Power down the control unit.
•
Attach a memory unit with compatible firmware.
FB14
Memory unit FW load failed The firmware on the attached
memory unit could not be
loaded to the drive.
•
Power down the control unit.
•
Check that the memory unit is properly inserted into the
control unit.
•
If the problem persists, replace the memory unit.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...