PS220 Configuration & Operation Guide
125 PS220
Function & F
eatures
Parameter Name
Value/Range
Note
13.12
AO1 SOURCE
MOTOR SPEED
[default]
Source selection parameters
(pointers) are used to configure
a signal for analog output. See
explanation above.
13.17
AO1 SOURCE MIN
-32767 to +32767
0 is the default
Defines the real minimum value
of the signal AO1 source that
corresponds to 0/4mA.
13.18
AO1 SOURCE MAX
-32767 to +32767
1500 is the default
Defines the real maximum
value of the signal AO1 source
that corresponds to 20mA.
13.19
AO1 OUT at AO1 Source
Min
0.00 to
22.00
mA 0mA
[default]
Defines desired lower limit of
Analog out signal in mA.
13.20
AO1 OUT at AO1 Source
Max
0.00 to
22.00
mA
20mA
[default]
Defines desired upper limit of
Analog out signal in mA.
13.22
AO2 SOURCE
MOTOR CURRENT
[default]
Source selection parameters
(pointers) are used to configure
a signal for analog output. See
explanation above.
13.27
AO2 SOURCE MIN
-32767 to +32767
0 is the default
Defines the scaled real minimum
value of the signal AO2 source
that corresponds to lowest mA
value.
13.28
AO2 SOURCE MAX
-32767 to +32767
100 is the default
Defines the scaled real
maximum value of the signal
AO2 source that corresponds
to highest mA. value
13.29
AO2 OUT at AO2 Source
Min
0.00 to
22.00
mA 0mA
is the
default.
Defines desired lower limit of
Analog out signal in mA.
13.30
AO2 OUT at AO2 Source
Max
0.00 to
22.00
mA 0mA
is the
default
Defines desired upper limit of
Analog out signal in mA.
Example of an “Other” choice for Analog Output:
To send the SMARTFLOW value out using Analog Output 1 (AO1) for a Flow range of 0-10000 GPM the following
parameters would be configured to:
Parameter 13.12: to SMARTFLOW.
Select other and then scroll to 1.217. Select
Configure Parameter 13.17 to 0
Configure Parameter 13.18: to 10000
Notes:
1. The default value for both AO1 and AO2 Parameters 13.19 and 13.29 is 0 mA
2 The scaling on the receiving side needs to be identical to what is configured on the PumpSmart PS220
3. Refer to the wiring diagrams in the back of this manual for details on these connections.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...