PS220 Configuration & Operation Guide
PS220 238
Functions &
Features
Parameter
Name
Value/Range
Notes
83.01
EXE P CLEAN SEQ
Defines how the cleaning sequence is executed.
NOT SEL (DEFAULT)
The pump cleaning sequence is disabled.
P CTRL DI3
The pump cleaning system is executed using DI3.
PS220
The pump cleaning system is executed by the
PS220 automatically.
83.02
REQ P CLEAN SEQ
Applicable only when 83.01 is set
to PS220.
Defines what triggers the request of the pump cleaning
sequence.
NOT SEL (DEFAULT)
Disable the Automatic execution of the PCS
TORQ
The request is triggered when 1.10 MOTOR TORQUE
exceeds the value set in 83.03 TORQ REQ for the
83.04 TON REQ.
Time of Day
This request is triggered when the time of day is
reached,
TORQ OR TIME of Day
This request is triggered by either motor torque or
run time.
83.12
REV RUN SPD
0.0-100.0%
80% [default]
Defines the reverse running speed in % of parameter
30.12, MAXIMUM SPEED.
83.13
REV RUN TIME
0.0-100.0 Seconds 7s
[default]
Defines the reverse running time of the pump cleaning
sequence.
83.14
REV RUN ACC
0.0-100.0 Seconds 2s
[default]
Defines the forward acceleration rate during the
execution of the cleaning cycle
83.15
REV RUN DEC
0.0-100.0 Seconds
01s [default]
Defines the reverse deceleration rate during the pump
cleaning sequence.
83.16
SEQUENCE TIMER
0-100 Seconds
30s [default]
.
83.17
SEQUENCE COUNTER
0-10
5 [default]
The number of times the PCS will run sequentially when
executed.
83.18
SEQUENCE EXCEED
Action and message displayed when the number of
sequences in 83.17 has been completed and the
torque value monitored is still at or above the value in
83.03. The default is FAULT.
DISABLED
The SEQUENCE EXCEED function is disabled and there
is no limitation on the number of PCS requests and
executions.
WARNING
The Keypad displays a warning PUMP CLOGGED and
the PCS function is disabled. The drive continues to
function in its normal configured state. A relay output
is energized and Fieldbus 3.11 PS Condition Word Bit 02
“PUMP CLOGGED” is set (if configured).
FAULT [default]
The drive faults and must be manually rese. The
Keypad displays a PUMP CLOGGED fault message.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...