PS220 Configuration & Operation Guide
PS220 176
Functions &
Features
To create a parameter Backup, follow these steps:
1. From the Home Screen: Menu> Backups>
2. Select create backup. If there is not a free backup slot in the control panel, skip to step 3.
3. Use the arrow key’s (right or down) to select one of the existing backup files, and press Replace.
4. Wait until the backup is completed. An animation is shown on the control panel during the backup process. The
control panel automatically returns to the Backups menu.
Note: If the backup process is canceled or interrupted, the previously saved backup file will not be deleted or dam-
aged.
To Restore a PS220 Configuration from a parameter Backup follow these steps:
1. Switch the Control Panel to “Local” Control
2. From the Home Screen Select Menu>Backups>use the Arrow keys to select the backup file you
want to restore from.
3. Arrow Down to “Restore All Parameters”
4. Push “Select”
5. Wait until the restore is completed. An animation is shown on the control panel during the restoring process. The
control panel automatically returns to the Backups menu when completed.
6. Switch Control Panel Back to Remote Mode.
Priming Delay
This feature is designed to allow Self-Priming pumps sufficient time to prime. The PumpSmart
PS220 will run at full speed for a preset time period. During the time frame configured all of the
PumpSmart logic becomes inactive. Once the priming time has elapsed all logic will then become
active. A warning message “Priming” will be displayed and acknowledged by the PS220.
Note:
In Multipump control when the system is started for the first time, as each PS220 receives a start
command, each will run the Priming function, and then will operate as required in Multipump
Mode. If a pump is taken offline for any reason once it is issued another start command, it will
also run the Priming function and then will operate as required in Multipump Mode.
Parameter
Name
Value/Range
Notes
75.02
PRIMING DELAY
0-6000 Seconds
0 [default]
This delay is active on every pump start, including
Multipump. During this time frame all of the control
logic is completely disabled.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...