PS220 Configuration & Operation Guide
201 PS220
Function & F
eatures
For Speed Control:
This procedure configures the PS220 keypad to set the speed reference for Setpoint 1 and for Setpoint 2.
The steps required as follows:
1. Configure the PS220 for Basic Startup and end with Basic Drive Setup. From the Home screen view, follow the
path: Menu>PS220 Configuration>Basic Startup>Basic Drive Setup>
2. Exit the assistants and go to group 22 (Speed reference selection): Follow the path:
Menu>Parameters>Complete List> Arrow down to Group 22>Select> Arrow down to: 22.11.
3. Configure 22.11 (speed Ref1 source) to “03.51- IEC Panel Reference”
1. “Edit”,
2. “Arrow Down” to “Other”
3. “Arrow Down” to 03 Input references
3. Select”
4. “Arrow Down “to 3.51 IEC panel reference.
5. Save””
6. “Arrow Down”
4. Configure 22.12(Speed Ref2 source) to “3.01 Panel Reference”
1. “Edit”,
2. “Arrow Down” to “Other”
3. “Arrow Down” to 03 Input references
3. Select”
4. “Arrow Down “to 3.51 IEC panel reference.
5. Save””
6. “Arrow Down” 2 times.
5. Configure 22.14 to “DI3” or any other available Digital input.
1. “Arrow Up to the DI to be used”
2. “Save”
3. “Back” 3 times.
6. Configure the Digital Input selected in step 5 with the PS220 Configuration Wizard. This will be choice (7)
when using the PS220 I/O Configuration Wizard.
7. Set min and max speed in group 30, if this has not been done previously, and then Start the PS220. Cycling
the Digital Input for the first time will have it run at Min speed until the reference is changed and saved. The
PS220 will then remember the 2 setpoints when cycling the Digital Input.
2. There is a separate/different configuration procedure for using any Analog input for Reference 2
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...