PS220 Configuration & Operation Guide
271 PS220
Parameter
Listing
Normally open
2W DI1 - 2W DI5
EXT1: 2-Wire assigned to DI1.
EXT2: 2-Wire switch at DI5.
This requires a preassigned switch (DI3) to switch between these choices.
All switches are “normally open”
FIELDBUS
Start via Fieldbus control word. External control location 1 only.
DI1P,2P – FB
Control at two external locations. EXT1: 3-Wire pulse start assigned to DI1 and pulse stop
assigned to DI2. EXT2: Fieldbus control word. This requires a preassigned switch (DI3) to
switch between these choices. DI1 and DI3 are normally open. DI2 is normally closed.
74.02
AUTO RESTART
Selects whether the PS220 will automatically restart after a power failure.
OFF [default]
Not selected
ON
Selected. The PS220 will automatically restart if conditions permit. Parameter 21.18 must be
0 seconds.
The function restarts the drive automatically and continues
operation after a supply break. Make sure that no dangerous
situations can occur.
74.03
STOP FUNCTION
Selects how the motor should stop during normal shutdown.
RAMP [default]
Pump shuts down using the ramp rate.
COAST
Power is cut immediately to motor allowing it to coast to a stop.
74.04
START DELAY
Once a start command is given the start delay will energize a relay which can be used to
turn-on an auxiliary lubrication system or other aux equipment prior to starting the motor.
Once the start delay has expired the PS220 will start the motor. The start delay does not
function in local control.
74.05
SPEED OVERRIDE
When active selects between PID control and Speed Control.
DISABLED (DEFAULT)
The Speed Override function is not active.
DI5
Activates speed override mode via a digital input 5.
DI5(INV)
Activates speed override mode via a digital input 5 inverse operation.
DI3
Activates speed override mode via a digital input 3.
DI3(INV)
Activates speed override mode via a digital input 3 inverse operation.
HOA
Activates speed override mode via digital input 2 hand function.
FIELDBUS
A fieldbus control word is used to activate the speed override mode.
74.06
SPD OVERRIDE REF
Defines the location of the override speed reference.
AI1
Selects analog input 1 as the override speed reference.
AI2
Selects analog input 2 as the override speed reference.
KEYPAD (DEFAULT)
Selects the keypad as the speed reference
FIELDBUS
Selects fieldbus as the speed reference set by FBA A Ref 1.
74.07
SPD OVERRIDE DFLT SPD
Defines the default value of the speed override speed reference. Default is 25% of motor
speed in 99.09
WARNING
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...