PS220 Configuration & Operation Guide
PS220 62
Pump & VFD
Protection
4.3. Secondary Protection Wizard
Secondary Protection uses onboard Digital Input switch connections from
any external device to provide a type of permissive, or inter-lock capability
to not allow the PS220 to run the pump. Examples of these are flow,
pressure, level switches, or many types of “Dry-Contacts” out from PLC
type devices.
Please refer to the Features & Functions section in this manual for a de-
tailed explanation of this functionality. This Wizard will show the step-by-
step instructions to configure this functionality for use.
This functionality can be configured with the PumpSmart PS220 Config-
uration Wizard. To access this Wizard from the Home Screen, follow the
path: Menu>PS220 Configuration>Pump & VFD Protection>Secondary
Protection>
The individual steps that will be performed are:
1. Configure the use Secondary of Protection A or B.
2. Configure the Protection Response.
3. Configure the Digital Input to be used.
4. Exit the Wizard.
1. Configure the use of Secondary Protection A or B.
1. “Arrow Right” (For using A)
2. “Arrow Up/Down” to Define
3. “Save”
4. “Next”
2. Configure the Protection Response.
1. “Arrow Up/Down” to Define
2. “Save”
3. “Next”
NOTE: YOU MAY SEE THIS ALARM MESSAGE AS
SOON AS YOU CONFIGURE THE RESPONSE.
SELECT “HIDE” AND CONTINUE.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...