PS220 Configuration & Operation Guide
175 PS220
Function & F
eatures
The table below lists all of the Parameters used in this function:
Parameter
Name
Value/Range
Notes
75.24
MULTIVAR CTL
OFF [default]
ON
Set to “ON” to enable the Multivariable functionality
75.25
MULTIVAR REF SOURCE
Analog Input 1
Analog Input 2
This parameter defines the source used in the
Multivariable control function. Choices are from any
available Analog Input. The selected Input will need to
be fully configured as “Proc Trans 2”
75.26
LEVEL 1
Range: 0-9999
0 [default]
This is the first level in which the Multivariable control
function will scale the set-point as it is defined by the
LO INTRCPT value and SP LO value. LEVEL 1 is defined
in units of the secondary process variable.
75.27
SP LO
Range: ±20000
0 [default]
This is the lower limit set-point as related to LO IN-
TRCPT. SP LO is defined in units of the primary process
variable or RPM when in speed control.
75.28
LO INTRCPT
Range: 0-9999
0 [default]
This is the lower limit level in which the Multivariable
function will scale the set-point as defined by the SP LO
value. LO INTRCPT is defined in units of the secondary
process variable.
75.29
LEVEL 2
Range: 0-9999
100 [default]
This is the upper level in which the Multivariable
control function will scale the set-point as it is defined
by the HI INTRCPT value and SP HI value. LEVEL 2 is
defined in units of the secondary process variable.
75.30
SP HI
Range: ±20000
0 [default]
This is the upper limit set-point as related to HI IN-
TRCPT. SP HI is defined in units of the primary process
variable or RPM when in speed control.
75.31
HI INTRCPT
Range: 0-9999
0 [default]
This is the upper limit level in which the Multivariable
function will scale the set-point as defined by the SP HI
value. HI INTRCPT is defined in units of the secondary
process variable.
Parameter Backup/Restoring
The PS220 has the ability to save all of the parameter settings configured to run the pump within
the Keypads on board memory. This is called a Backup. This backup will also allow the ability to
restore all parameter settings if the need arises. Two pump configuration backup files can be cre-
ated using this function. This may allow you to reconfigure the drive to operate separate configu-
rations for the same pump in service.
The Backup Functionality also can create an “Automatic backup”. This is created two hours after
any parameter changes, or if a backup was not created manually. After 24 hours the ”Automatic
Backup Function” completes a compare function, which compares the existing backup to how the
PS220 is currently configured, and again will automatically create a new backup overwriting the
previous one. When viewing the backup files, there will be “Folded Page Icon” with the letter “A”
shown on the top left corner signifying that this was Automatically created. See the Screen shot
below:
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...