PS220 Configuration & Operation Guide
265 PS220
Parameter
Listing
GROUP 5
DIAGNOSTICS
DESCRIPTION
Scaling
5.01
ON-TIME COUNTER
On-time counter. The counter runs when the drive is powered. (0-65535 days)
1=1 day
5.02
RUN-TIME COUNTER
Motor run-time counter. The counter runs when the inverter modulates. (0-65535 days)
1=1 day
5.04
FAN ON-TIME COUNTER
Running time of the drive cooling fan. Can be reset from the control panel by keeping Reset
depressed for over 3 seconds. (0-65535 days)
1=1 day
5.09
TIME FROM POWER-UP
500-microsecond ticks elapsed since the last boot of the control unit. (0-4294967295)
1=1
5.11
INVERTER TEMPERATURE
Estimated drive temperature in percent of fault limit. The actual trip temperature varies
according to the type of the drive. (40.0-160.0%)
•
0.0% = 0 °C (32 °F)
•
94% approx. = Warning limit
•
100.0% = Fault limit
1=1%
5.22
DIAGNOSTIC WORD 3
Diagnostic word 3.
1=1
5.41
MAIN FAN SERVICE COUNTER
Displays the age of the main cooling fan as a percentage of its estimated lifetime. The
estimate is based on the duty, operating conditions and other operating parameters of the
fan. When the counter reaches 100%, a warning is generated. Can be reset from the
control panel by keeping Reset depressed for over 3 seconds. (0-150%)
1=1%
5.42
AUX. FAN SERVICE COUNTER
Displays the age of the auxiliary cooling fan as a percentage of its estimated lifetime. The
estimate is based on the duty, operating conditions and other operating parameters of the
fan. When the counter reaches 100%, a warning is generated. Can be reset from the
control panel by keeping Reset depressed for over 3 seconds. (0-150%)
1=1%
GROUP 6
CONTROL & STATUS WORDS
DESCRIPTION
Scaling
6.01
MAIN CONTROL WORD
The main 16 bit control word of the drive. The bit assignments of the word are as described
in the ACS880 Firmware Manual. This parameter is read-only in Hex.
HEX
6.02
APPLICATION CONTROL WORD
Reference the ABB ACS880 Firmware Manual for parameter definition.
6.03
FBA A TRANSPARENT CONTROL
WORD
Displays the unaltered control word received from the PLC through fieldbus adapter A when
a transparent communication profile is selected. This parameter is read-only.
(00000000h-FFFFFFFFh)
HEX
6.04
FBA B TRANSPARENT CONTROL
WORD
Displays the unaltered control word received from the PLC through fieldbus adapter B when
a transparent communication profile is selected. See section Control word and Status word
in the ACS880 Firmware Manual. This parameter is read-only. (00000000h-FFFFFFFFh)
HEX
6.05
EFBA TRANSPARENT CONTROL WORD Displays the unaltered control word received from the PLC through the embedded
fieldbus interface when a transparent communication profile is selected in parameter
58.25 Control profile. See section The Transparent profile in the ACS880 Firmware Manual.
This parameter is read-only. (00000000h-FFFFFFFFh)
HEX
6.11
MAIN STATUS WORD
Main 16 bit status word of the drive. Parameter is read-only. (0000h-FFFFh)
HEX
6.16
DRIVE STATUS WORD 1
Drive status word 1. This parameter is read-only. See the ACS880 Firmware Manual for bit
assignment.
BINARY ACTUAL
BITS
6.17
DRIVE STATUS WORD 2
Drive status word 2. This parameter is read-only. See the ACS880 Firmware Manual for bit
assignment.
BINARY ACTUAL
BITS
6.18
START INHIBIT STATUS WORD
Start inhibit status word. This word specifies the source of the inhibiting condition that is
preventing the drive from starting. After the condition is removed, the start command must
be cycled. See bit-specific notes. See also parameter 06.25 Drive inhibit status word 2, and
06.16 Drive status word 1, bit 1. This parameter is read-only. See the ACS880 Firmware
Manual for bit assignment. (0000h-FFFFh)
BINARY ACTUAL
BITS
6.19
SPEED CONTROL STATUS WORD
This parameter is read-only. See the ACS880 Firmware Manual for bit assignment.
(0000h-FFFFh)
BINARY ACTUAL
BITS
6.20
CONSTANT SPEED STATUS WORD
Constant speed/frequency status word. Indicates which constant speed or frequency is
active (if any). See also parameter 06.19 Speed control status word, bit 7, and section
Constant speeds/frequencies (page 43). This parameter is read-only. See the ACS880
Firmware Manual for bit assignment. (0000h-FFFFh)
BINARY ACTUAL
BITS
6.21
DRIVE STATUS WORD 3
This parameter is read-only. See the ACS880 Firmware Manual for bit assignment.
(0000h-FFFFh)
BINARY ACTUAL
BITS
6.25
DRIVE INHIBIT STATUS WORD 2
This word specifies the source of the inhibiting condition that is preventing the drive from
starting. After the condition is removed, the start command must be cycled. See bit-specific
notes. See also parameter 06.18 Start inhibit status word, and 06.16 Drive status word 1, bit
1. This parameter is read-only. See the ACS880 Firmware Manual for bit assignment.
(0000h-FFFFh)
BINARY ACTUAL
BITS
6.29-6.101
VARIOUS ACS880 CONTROL AND
STATUS WORDS
Reference the ABB ACS880 Firmware Manual for parameter definition.
—
6.200
PUMP STATUS
The 16 bit Pump Status Word for the PS220
BINARY ACTUAL
BITS
6.201
PUMP WATER FEATURE CW
The 16 bit PS220 Control Word for the PumpSmart water functions
BINARY ACTUAL
BITS
6.202
PUMP WATER FEATURE SW
The 16 bit PS220 Status Word for the PumpSmart water functions
BINARY ACTUAL
BITS
6.203
PUMPSMART ALARM WORD 1
The 16 bit PS220 Alarm word 1 (16 bit)
BINARY ACTUAL
BITS
6.204
PUMPSMART ALARM WORD 2
The 16 bit PS220 Alarm word 2 (16 bit)
BINARY ACTUAL
BITS
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...