PS220 Configuration & Operation Guide
PS220 38
SmartFlow
Prior to executing this function:
1. All Suction and Discharge piping should be secure and ready for Pump startup.
2. Pump and motor aligned and coupled with coupling guard intact.
3. Suction line needs to be completely flooded and all air vented completely from the pump through to
the discharge side.
4. Discharge valve or isolation valve and any bypass piping need to be completely closed.
5. For seal-less pumps having liquid lubricated bearings consult with the manufacturer verify if the pump
can be run for 35 seconds against a closed discharge valve with the liquid that is to be pumped at the
speeds noted below.
Answer the questions and follow the instructions on the screens:
This screen shot shows the end of a completed successful Smartflow
Tune. There will be 2 active warnings shown and then this screen will
disappear and you will prompted to continue.
Never operate rotating equipment unless all protective coupling and shaft
guards are in place. Personal injury may occur if the driven equipment is
operated without coupling and shaft guards.
WARNING
Failure to follow the guidelines in this section
can result in serious physical injury, death
and/or equipment damage.
DANGER
Observe all CAUTIONS and WARNINGS highlighted in the ABB ACS880
Hardware Manual, and the PumpSmart PS220 Configuration Manual
prior to starting.
WARNING
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...