PS220 Configuration & Operation Guide
PS220 68
Pump & VFD
Protection
4. Configure the Condition 1 Alarm Limits High (and/or Low) Value (If Necessary)
1. “Arrow Right” to change
2. “Arrow Up/Down” to define
3. “Save”
4. “Arrow Down”
Repeat steps 1- 4 again (If necessary)
5. Configure the Condition 1 Response Delay time.
The Default is 20 Seconds. The range is 0- 3600 seconds.
1. “Arrow Right” to change
2. “Arrows UP/DOWN” to Define
3. “Save”
4. “Arrow Down”
6. Configure the Min Speed Stop Delay time.
When the monitored condition triggers a Warning or Alarm, the PumpSmart PS220 can be configured to run at its
minimum speed for a timed duration. If the condition that triggered the warning has not cleared during this time, the
drive will fault off and stop. This is not a re-settable fault. The fault will have to be reset, and the drive issued a start
command again. Please refer to the section “Fault Tracing” in this manual. The Default is 0, which disables this
function. The range is (0- 3600 seconds)
1. “Arrow Right”
2. “Arrows to Define”
3. “Save”
4. “Arrow Down”
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...