PS220 Configuration & Operation Guide
123 PS220
Function & F
eatures
Analog Inputs
The PumpSmart PS220 has two configurable analog inputs as standard. By default,
both inputs are current sourced and set to a scaled value of 4 to 20 mA. Each can
be independently changed to a 0 to 10VDCvoltage sourced input by changing a
jumper position on the control board. See the Pic below:
The jumpers by default are in the 2 top positions on both inputs.
Each input can also be undependably filtered, inverted, and scaled. The number of
analog inputs can be increased to five by installing an optional FIO-11 I/O extension
card in slot 3 on the control board.
When using many of the PS220 Configuration wizards, the inputs that you need
will automatically be configured. If you need to incorporate additional inputs that
have not yet been configured to complete your configuration, you can use the
PS220 configuration Wizard.
To add the FIO-11 I/O extension card from the home view follow the path:
Menu>PS220 Configuration> I/O Configuration>Yes > Wait for the software to load.
When configuring an Analog Input, you will need the information listed in the tables below:
Table 1. Identity’s what the Individual Analog Input will be used for, or its Name configuration.
These choices are listed in the table below. For both IA1 and AI2:
Parameter Name
Value/Range
NOTES
76.01 or
76.02
AI1 CONFIG or
AI2 CONFIG
PROC TRANS 2
Used for the Multivariable control functionality.
PROC TRANS 1
Used as the primary process transmitter for Control Mode.
EXT SETPOINT1
Used for the Primary External Setpoint
EXT SETPOINT2
Used for a Secondary External Setpoint for the Dual Setpoints
functionality.
FLOWMETER
Used when Flow is used for the Control Mode or for use
with Smartflow Pump Protection
DISCH PRESSURE
Used with Advanced SmartFlow.
SUCTION PRESS
Used with Advanced SmartFlow
DIFF PRESS
Used with Advanced SmartFlow
TEMPERATURE
Used when Temperature is the primary Control Mode or when a
temperature transmitter is required for Specific Gravity
correction with Smartflow.
VISC/SG VALUE
Used when a correction is required for Specific Gravity
with Smartflow.
SPD OVRRD
Used for the external reference for the Speed Override
functionality.
LEVEL
Used when Level is the primary process transmitter for Control
Mode.
FLOW REF
Used for the Primary External Setpoint for the Flow Control
Mode
PRESSURE REF
Used for the Primary External Setpoint for the Pressure Control
Mode
TEMPERATURE REF
Used for the Primary External Setpoint for the Temperature
Control Mode
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...