PS220 Configuration & Operation Guide
PS220 124
Functions &
Features
Table 2. Identity’s what the Individual Analog Inputs electrical attributes are.
These choices are listed in the table below. For both IA1 and AI2:
12.27
AI2 MIN
Defines the minimum value for analog input AI2.(0-22mA or 0-10V)
12.28
AI2 MAX
Defines the maximum value for analog input AI2. (0-22mA or 0-10V)
12.29
AI2 SCALED AT AI2 MIN
Defines the real value that corresponds to the minimum analog input AI2 value defined by parameter 12.27 AI2
min. The range is -32767.000 - 32767.000
12.30
AI2 SCALED AT AI2 MAX
Defines the real value that corresponds to the maximum analog input AI2 value defined by parameter 12.28 AI2
max. The range is -32767.000 - 32767.000
GROUP 12
ANALOG INPUTS
DESCRIPTION
12.15
AI1 UNIT SELECTION
Selects the electrical unit for readings. Note: This setting must match the corresponding hardware setting on the
drive control unit. See Basic Wiring drawing in appendix A4. (mA or V)
12.17
AI1 MIN
Defines the minimum value for analog input AI1. (0-22mA or 0-10V)
12.18
AI1 MAX
Defines the maximum value for analog input AI1. (0-22mA or 0-10V)
12.19
AI1 SCALED AT AI1 MIN
Defines the real internal value that corresponds to the minimum analog input AI1 value defined
by parameter 12.17 AI1 min. The range is -32767.000 - 32767.000.
12.20
AI1 SCALED AT AI1 MAX
Defines the real internal value that corresponds to the maximum analog input AI1 value defined by parameter 12.18
AI1 max. The range is -32767.000 - 32767.000
12.25
AI2 UNIT SELECTION
Selects the electrical unit for readings. This setting must match the corresponding hardware setting on the drive
control unit.
NOTE: To change from Current sourced to Voltage sourced on the individual inputs change the
Jumpers as follows: J1 for AI1 and J2 for AI2. See the Pic below:
Analog Outputs
The PumpSmart PS220 has two configurable analog outputs as standard. By default, both outputs are current sourced
and set to a value of 0 to 20 mA. These outputs can be configured to any Signal in the Group 1 parameters. There is
also a configurable choice for “Other” to define custom outputs if so required. Each choice will need to have a pre-
defined scale, Minimum and Maximum associated with it.
See the table below for Parameters Configuration
Notes:
1. The number of analog outputs can be increased to three by installing FIO-11 or FAIO-01 I/O extension card in slot 3
on the control board.
2. The default choices for both outputs are listed in the table below. You can use this configuration Wizard to change
them as needed to complete your configuration.
3. The Wizard will allow you to add the FIO-11 I/O extension card.
To add the FIO-11 or FAIO-01 I/O extension card (Must be in Slot#3) from the home view follow the path
Menu>PS220 Configuration> I/O Configuration>Yes>Wait for the software to load.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...