PS220 Configuration & Operation Guide
PS220 222
Functions &
Features
The table below lists all of the Parameters that may be used during the configuration of the Specific
Gravity when using the Smartflow Wizard. The description of these parameters is also listed in the
index under Parameter Listings.
Parameter
Name
Value/Range
NOTES
76.01
AI1 CONFIG
See the choices below
76.02
AI2 CONFIG
PROC TRANS 2
Used with Multivariable control.
PROC TRANS 1
The primary process transmitter. The units and
transmitter scaling AI1 Max and AI1 Min must also
be set.
EXT SETPOINT1
Used when fixed or variable setpoint is sent via an
external source to setpoint 1
EXT SETPOINT2
Used when fixed or variable setpoint is sent via an
external source to setpoint 2
FLOWMETER
Used when a flow meter is selected for use
with Advanced Pump Protection,
DISCH PRESSURE
Used with Advanced SmartFlow. Identifies the
location of the discharge pressure transmitter.
SUCTION PRESS
Used with Advanced SmartFlow. Identifies the
location of the suction pressure transmitter.
DIFF PRESS
Used with Advanced SmartFlow. Identifies the
location of the differential pressure transmitter.
TEMPERATURE
Used when a temperature transmitter is being used
for SG / VISC correction with Smartflow.
VISC/SG VALUE
Used if setting SG or VISC directly using an
analog input with SmartFlow.
SPD OVRRD REF
Used when setting a speed override reference.
78.02
SG SELECT
SG RATE [default]
Used for applications where S.G. is constant.
SG CALC (T)
Use for applications where S.G. varies. A temperature
measuring instrument must be wired to an open analog
input channel.
AI
S.G. is sent via an external analog input signal
DI
S.G. is toggled between two values (SG MIN and SG
MAX) via Digital Input 5. SG MIN = DI5 open, SG MAX
= DI5 closed. Selecting DI in 78.02 automatically con-
figures DI5 in parameter 76.13 to SG SELECT.
78.03
SG RATED
1.0 [default]
Setting range is 0 – 10.0.
78.04
SG MIN
1.0 [default]
Setting range is 0 – 10.0.
78.05
SG MID
1.0 [default]
Setting range is 0 – 10.0.
78.06
SG MAX
1.0 [default]
Setting range is 0 – 10.0.
78.07
TEMP RATED
104ºF English(US)
50ºC All Other Languages
Temperature of pumped liquid at SG RATE. Setting
range: -200 to 1000
79.08
T MIN
0ºF English(US)
0ºC All Other Languages
Temperature of pumped liquid at SG MIN. Setting range:
-200 to 1000.
79.09
T MAX
212ºF English(AM)
100ºC All Other Languages
Temperature of pumped liquid at SG MAX. Setting
range: -200 to 1000.
79.10
T RATE
104ºF English(AM)
50ºC All Other Languages
Temperature of pumped liquid at SG RATE. Setting
range: -200 to 1000
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...