7.3 PIPE CLEANING FUNCTION WIZARD
The PS220’s Pipe Cleaning function will allow for a high flow flushing of the
discharge piping system. This will reduce sedimentation that may have accu-
mulated in the piping and he overall wear on the piping system over time. The
PS220 can be configured to execute the pipe clean sequence on every start, or
strictly based on actual accumulated pump/motor running hours. The pump
will be run at full speed when this function is executed.
When the Pipe Cleaning function is initiated, all PS220 functional control is
disabled except for Pump Protection. It is automatically enabled once the
function completes.
When the Pipe Cleaning function is active the message “Pipe Clean Running”
will be displayed on the Keypad and will be captured and stored in the event
log.
Please refer to the Pipe Cleaning section in this manual for a more detailed
explanation of this functionality. This Wizard will show the step-by-step
instructions to configure the Pipe Clean Function for use. This functionality can
be configured with the PumpSmart PS220 Configuration Wizard. To access
this Wizard from the Home View, follow the path: Menu>PS220 Configura-
tion>Water Function>Pipe Cleaning Function>l
The individual steps that will be performed are:
1. Configure the method to enable Pipe Cleaning function.
2. Configure the Pipe Clean Time interval,
3. Configure the Pipe Clean Cycle Time.
4. Exit the Wizard
The Screen Shots that follow will show you step by step, how to configure this
functionality.
1. Configure the method to enable Pipe Cleaning function.
The two selection choices are:
1. At every Start command
2. Based on an accumulated run time interval.
1. “ARROW RIGHT” To change
2. “ARROW UP/DOWN” to change value
3. “Save”
4. “ARROW DOWN”
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...