PS220 Configuration & Operation Guide
65 PS220
Pump & VFD Protection
NOTE:
1. When Selecting Proc. Trans 1, the Wizard will ask you to confirm all of the settings for its use. You will need to:
1. Confirm the AI it is wired to.
2.Confirm the Min. scaling, Max. Scaling, and the units
2. When Selecting Proc. Trans 2, (if it has not already been configured previously) the Wizard will ask you to:
“Save”
1. Configure the AI it is wired to.
1. “Arrow Up/Down” to select.
2. “Select”
2. Configure the AI Min. scaling.
1. “Arrow Right”
2. “Arrow Up/Down” to change
3. “Save”
4. “Arrow Down”
3. Configure the AI Max. Scaling.
1. “Arrow Right”
2. “Arrow Up/Down” to change
3. “Save”
4. “Arrow Down”
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...