PS220 Configuration & Operation Guide
PS220 202
Functions &
Features
The table below shows that Digital Input 3 is defaulted to be used for the Dual Setpoint Function
Parameter
Name
Value/Range
Notes
76.11
DI3
DUAL STPT SEL
This is the Default setting for this parameter. This selection will use
setup digital input DI3 to toggle between set-point 1 and set-point
2. DI3 low is Setpoint 1; DI3 High is Setpoint2. Any available DI can
be used for this function. DI3 is the default.
For Multipump this MUST BE WRIED IN SERIES between all drives.
EXAMPLE:
Process Control PID with the primary 4- 20 mA Transmitter wired to AI1 with the primary set
point, which can be varied wired to AI2. Either Analog Input can be either Current or voltage.
Parameter
Name
Value/Range
Notes
76.01
AI1 CONFIG
Proc Trans 1
control
76.02
AI2 CONFIG
EXT T Setpoint
AI2 used for EXT 1 Setpoint
( It can be varied)
Note: The effect is a straight relationship with the maximum set-point value corresponds to the
maximum signal [i.e. 20 mA or 10 VDC] while the minimum set-point value corresponds to the
minimum signal [0/4mA or 0/2 VDC].
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...