PS220 Configuration & Operation Guide
273 PS220
Parameter
Listing
EXT SETPOINT2
Used for a Secondary External Setpoint for the Dual Setpoints functionality.
FLOWMETER
Used when Flow is used for the Control Mode or for use with Smartflow
Pump Protection
DISCH PRESSURE Used with Advanced SmartFlow.
SUCTION PRESS
Used with Advanced SmartFlow
DIFF PRESS
Used with Advanced SmartFlow
TEMPERATURE
Used when Temperature is the primary Control Mode or when a temperature
transmitter is required
for Specific Gravity correction with Smartflow.
VISC/SG VALUE Used when a correction is required for Specific Gravity with Smartflow.
SPD OVRRD
Used for the external reference for the Speed Override functionality.
LEVEL
Used when Level is the primary process transmitter for Control Mode.
FLOW REF
Used for the Primary External Setpoint for the Flow Control Mode
PRESSURE REF
Used for the Primary External Setpoint for the Pressure Control Mode
TEMPERATURE REF Used for the Primary External Setpoint for the Temperature Control Mode
NOT SELECTED
Not used
`76.03-05
AIOPT1 ,AIOPT2, AIOPT3
Configuration
Same choices
as above
Same choices as above
76.06
RO1 SOURCE (Default is Ready)
Selects the PS220 status to be indicated through relay outputs 1 selection. The relay
energizes when the status meets the setting.
(0) FORCE OFF
Relay is nonfunctional.
(1) FORCE ON
Force the Relay output to be active.
(2) FAULT
A general VFD or PUMP related fault has occurred. Normally Closed.
(3) RUNNING
Drive is running the motor.
(4) FLOW BYP SMRT FLW
Minimum flow bypass is active using Smartflow.
(5) PIPE CLEAN
A pipe cleaning sequence is being executed.
(6) COND1 HI ALARM
Condition 1 HI Alarm is active.
(7) COND2 HI ALARM
Condition 2 HI Alarm is active.
(8) FLOW BYP EXT FLW
Minimum flow bypass is active using an external flowmeter.
(9) PUMP FLTS/WRNGS
A general pump related warning or fault has occurred.
(10) READY
Drive is ready to run.
(11) SECND PRTECT A
Secondary Protect A activation.
(12) SECND PRTECT B
Secondary Protect B activation.
(13) PCS REQ
A pump cleaning sequence has been requested.
(14) PCS EXE
A pump cleaning sequence is being executed.
(15) PUMP PROTECT
Pump protection is active.
(16) MULTI VAR ACTIVE
Multivariable control is active.
(17) SPEED OVERIDE
Speed override is active.
(18) COND1 LOW ALARM
Condition 1 LOW Alarm is active.
(19) COND2 LOW ALARM
Condition 2 LOW Alarm is active.
(20) START DELAY ACTIVE
Start Delay function is active.
(21) REMOTE
Drive is in remote mode.
(22) INV FAULT
A general VFD or PUMP related fault has occurred. Inverted operation.
OTHER
A specific parameter setting is active.
76.07
RO2 SOURCE (Default is Running)
Selects the PS220 status to be indicated through relay outputs 1 selection. The relay
energizes when the status meets the setting. Same 24 choices as 76.06.
76.08
RO3 SOURCE (Default is Fault)
Selects the PS220 status to be indicated through relay outputs 1 selection. The relay
energizes when the status meets the setting. Same 24 choices as 76.06.
76.09
DI1
Selects the Digital input 1 function Refer to configuration guide for choices
76.10
DI2
Selects the Digital input 2 function Refer to configuration guide for choices
76.11
DI3
Selects the Digital input 3 function Refer to configuration guide for choices
76.12
DI4
Selects the Digital input 4 function Refer to configuration guide for choices
76.13
DI5
Selects the Digital input 5 function Refer to configuration guide for choices
76.14
DI6
Selects the Digital input 6 function Refer to configuration guide for choices
76.15
DIO1
Selects whether DIO1 is used as a digital input. Options are the same as the DI’s.
76.16
DIO2
Selects whether DIO2 is used as a digital input. Options are the same as the DI’s.
76.17
DIO1 OUTPT SOURCE
Selects the PS220 status to be indicated through relay outputs DO1 selection. The relay
energizes when the status meets the setting. DO1 is limited to 200 MA with the 24vDC pin.
Same 24 choices as 76.06.
76.18
DIO2 OUTPT SOURCE
Selects the PS220 status to be indicated through relay outputs DO2 selection. The relay
energizes when the status meets the setting. DO2 is limited to 200 MA with the 24vDC pin.
Same 24 choices as 76.06.
GROUP 77 SMARTFLOW
DESCRIPTION
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...