PS220 Configuration & Operation Guide
153 PS220
Function & F
eatures
The PumpSmart PS220 can identify when a Minimum flow event is occurring and provide several responses as
noted below:
When configuring the use of the Minimum Flow Control you will need to select a Response and define the
actual Minimum flow value.
The choices are:
A. Disabled (Default)
The PumpSmart PS220 will continue to run. There will not be any indication of this event.
B. Alarm (Warning).
The PumpSmart PS220 will continue to run. The warning message “Min Flow Warning” will display. The event
will be stored in the Event Log. It will
continue to indicate the warning until the flow increases to a value
above minimum flow.
C. Alarm & Control
The PumpSmart PS220 will indicate that the pump is running at or below minimum with a message “Min Flow
Warning”. After the response delay time has expired. The event will be stored in the Event Log. The PS220 will
then respond based on the configured Protections Options. When a Hard Fault occurs, it will display the mes-
sage “Min Flow Fault”. It will have to be reset and manually restarted.
Please refer to the section “Fault Tracing” and “Protection Options” in this manual for more information on
these topics.
This functionality can be configured with the PumpSmart PS220 Configuration Wizard.
To access this Wizard from the Home Screen, follow the path: MENU>PS220 Configuration>Pump & VFD
Protection>Pump Protection>No>Yes or No> Follow the prompts
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...